Skip to main content

Product Description

These products comprise a 1200mm length of semi-rigid Euro class A1 mineral Rock fibre slab fully encapsulated within a 38 micron polythene film. This is tested to the latest EN 1366-4:2009/EN 1363:1 2012 and BS 476 20: 1987

Applications

Primarily designed to prevent fire penetration, the StoneShield TCB product range maintains thermal insulation integrity and reduces sound transmission within the cavities of buildings. Stoneshield TCB products are available to fit a wide range of cavity widths within masonry, timber frame and steel panel constructions and are equally suitable for installation around apertures and at floor level in partition walls. When installed in the above types of construction Stoneshield TCB’s meet the insulation requirements of Approved Document L1A (England & Wales: October 2010).

Installation

For use within timber frame construction with a brick or block outer skin, Stoneshield TCB products are supplied with flanges incorporated into the polythene outer sleeve. These enable the barriers to be held in place until the brickwork is complete. The TCB product is fixed to the timber frame using non-corrosive large head nails or staples at 150mm centers, with the subsequent construction of the brickwork maintaining a minimum compressive contact with the barrier as shown. The TCB at the corners should overlap to ensure a close butted fit is achieved to close the cavity.

In the case of masonry outer skin to masonry inner skin or steel frame construction, Stoneshield TCB products are supplied with unflanged polythene Outer sleeves. Barrier size is selected so that the TCB forms a friction fit within the cavity with minimum compression. Care should be taken in respect of joints, which should be closely butted together.

In the case of apertures such as windows or doors where barriers are friction fitted, it is important that the horizontal barrier overlaps the vertical
barrier at the corner joints.

Technical

Stoneshield TCB products have been extensively tested by Exova Warringtonfire. Several test samples have been undertaken and assessments conducted as foreseen in warres 316443A

The 50mm x 50mm entry level item within the product range provides in excess of the 30 minute cavity fire barrier requirement defined in Table 6 of Appendix A to Approved Document B, Building Regulations 2022 onwards. Moving through the product range, performance levels increase to in excess of 60 minutes integrity and insulation. The following Performance Tables are included to assist in selecting an appropriately-sized barrier for a given application.

Performance Tables

30 Minutes Integrity

Max Cavity Width (mm) Barrier Width (mm) Barrier Depth (mm) Colour
40 55 65 Red
50 65 65 Red

30 Minutes Integrity + 15 Minutes Insulation

Max Cavity Width (mm) Barrier Width (mm) Barrier Depth (mm) Colour
50 65 65 Red

30 Minutes Integrity + 30 Minutes Insulation

Max Cavity Width (mm) Barrier Width (mm) Barrier Depth (mm) Colour
40 50 75 Red
50 60 75 Red
60 70 75 Red
70 80 75 Red
80 90 75 Red
90 100 100 Green
100 110 100 Green
110 120 100 Green
120 130 100 Blue
130 140 100 Blue
140 150 100 Yellow

60 Minutes Integrity

Max Cavity Width (mm) Barrier Width (mm) Barrier Depth (mm) Colour
40 55 110 Red
50 65 110 Red
60 75 110 Red
70 85 110 Red
80 95 110 Green
85 100 110 Green

60 Minutes Integrity + 60 Minutes Insulation

Max Cavity Width (mm) Barrier Width (mm) Barrier Depth (mm) Colour
40 55 145 Green
50 65 145 Green
60 75 145 Green
70 85 145 Green
80 95 145 Green
90 105 145 Blue
100 115 145 Blue
110 125 145 Blue
120 135 145 Yellow
130 145 165 Yellow
140 155 165 Yellow